Feature
- 2U chassis design, high integrated, modularization.Support speaker circuit grounding, open circuit and short circuit detection.
- Support 3/4 wire horn circuit wiring.
- 8 programmable trigger input interfaces.
- 8 programmable trigger output interfaces.
- Support power-saving mode when the amplifier has not input signal enters.
- Support lines redundance wiring.
- Support linkage to fire alarm controller.
- * Main amplifier automatic backup switching power amplifier, real-time detection, indicate by different color LEDs.
- * Real time monitoring speaker bus loop, power amplifier status, automatic control switch.
- * Allows amplifier enter into power saving mode when no signal input to save energy (start through VA-6000ST, default disabled).
- * Allows to configure the priority of network and local audio.
- * Support power through, even if the main and standby power supply is cut off at the same time (amplifier power supply normal), the local 8 audio signals are not affected.
- * 8 stem node or wet node input port, to trigger the pre-pragrammed language information to the specified zones or open the coresposing external power to the corresponding event warning.
- * 8 programmable relay signal output port, ouupt no voltage output short circuit relay control signal to the third party equipment to realize on-line automatic control.
- * Provide DC 24V standby power input interface ( connect to 24V DC supplied by VA-6000BC).
Specifications:
Model | VA-6000MS |
AC Power Supply | |
Voltage | ~220-240V 50/60Hz |
Maximum Current | 0.3A (not including the 4 wire strong cut output) |
Specification Of The Fuse | 250V/2A, slow speed type |
DC Power Supply | |
Voltage | 24V DC, ±20% |
Maximum Current | 2A (not including the 4 wire strong cut output) |
Power | 48W |
Performance Index | |
Parallel Signal Input / Output | |
Distortion | <1% (rated output power),1KHz |
Frequency | 80Hz~20KHz |
Sensitivity | 385mV |
Impedance | 10KΩ |
S/N Ratio | >70dB |
Contact Output | |
8 Relay Programmable Output | Short circuit, no voltage |
8 ProgrammableTrigger Input | 8 programmable trigger input |
Level Model | Highest 3.3V |
Short Circuit Mode | No voltage, short circuit |
Cooling Way | Air cooled |
Protection | Delay / temperature / short / overload |
Mechanical Index | |
Size (L x W x D) | 484 x 88 x 447 mm (19 inches wide, 2U) |
Weight | About 7.8 Kg |
Installation | Desktop or 19 inch cabinet |
Color | Black |
Environmental Requirements | |
Environmental Requirements | +5℃ ~ +40℃ |
Storage Temperature | -20℃ ~ +70℃ |
Relative Temperature | <95% (no treatment) |